| | SLO | ENG | Cookies and privacy

Bigger font | Smaller font

Show document Help

Title:ANALIZA VPLIVA TOKOVNIH RAZMER NA ZMANJŠEVANJE KONCENTRACIJE PLINOV V LABORATORIJSKEM DIGESTORIJU
Authors:ID Jeke, Uroš (Author)
ID Hriberšek, Matjaž (Mentor) More about this mentor... New window
Files:.pdf UNI_Jeke_Uros_2010.pdf (3,45 MB)
MD5: EA4FB803D4B79E6904314CCD1BFD3D7B
PID: 20.500.12556/dkum/5449a764-f193-4e90-a379-1684ebd38b51
 
Language:Slovenian
Work type:Bachelor thesis/paper
Organization:FS - Faculty of Mechanical Engineering
Abstract:Digestorij je osrednja procesna naprava za zagotavljanje varnosti v laboratoriju. V podjetju Krka d.d. so v delovni prostor nekaterih naprav zaradi priročnosti namestili police, na katerih hranijo kemikalije. Modificiran delovni prostor ima drugačno uspešnost pri odplinjanju škodljivih plinov kot nespremenjen. S pomočjo računalniške dinamike tekočin sem simuliral dogajanje v delovnem prostoru brez polic in z nameščenimi policami. Večja kot je vtočna površina, uspešnejše je odnašanje plina. Pri zaprtem vtočnem oknu se koncentracija plina v delovnem prostoru zmanjšuje hitreje v primeru z nameščenimi policami. Z odpiranjem okna se razmere obrnejo. Glede na naravo dela in pogostost posegov med kemijskimi preizkusi, je za zagotavljanje večje varnosti zaposlenih potrebno police odstraniti.
Keywords:digestorij, računalniška dinamika tekočin, tokovno polje, varnost v laboratoriju
Place of publishing:Maribor
Publisher:[U. Jeke]
Year of publishing:2010
PID:20.500.12556/DKUM-16028 New window
UDC:532:662.042.3(043.2)
COBISS.SI-ID:15035670 New window
NUK URN:URN:SI:UM:DK:ZAGOUC1B
Publication date in DKUM:01.10.2010
Views:3058
Downloads:299
Metadata:XML DC-XML DC-RDF
Categories:KTFMB - FS
:
JEKE, Uroš, 2010, ANALIZA VPLIVA TOKOVNIH RAZMER NA ZMANJŠEVANJE KONCENTRACIJE PLINOV V LABORATORIJSKEM DIGESTORIJU [online]. Bachelor’s thesis. Maribor : U. Jeke. [Accessed 26 March 2025]. Retrieved from: https://dk.um.si/IzpisGradiva.php?lang=eng&id=16028
Copy citation
  
Average score:
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
(0 votes)
Your score:Voting is allowed only for logged in users.
Share:Bookmark and Share


Hover the mouse pointer over a document title to show the abstract or click on the title to get all document metadata.

Secondary language

Language:English
Title:FLOW FIELD BASED INFLUENCE ANALYSIS OF CONCENTRATION DECREASE IN LAB DIGESTORIUM
Abstract:Digestorium is a central processing device for safety insurance in the lab. In the Krka d.d. company shelves were installed into working spaces of several devices. It is more convenient, since they are used for chemical storage. Modified working space has a different efficiency at the removal of toxic gasses as the original one. With the help of Computational Fluid Dynamics I simulated events which take place in the modified and original working space. The bigger the inflow gets, the better is the removal of toxic gasses. With a closed inflow window, the concentration of toxic gasses drops faster with installed shelves. If we open the inflow window, the concentration drops faster at original working space. Regarding the high frequency of interventions into the working space during chemical experiments, shelves should be removed to ensure a better safety.
Keywords:digestorium, computational fluid dynamics, current field, safety in lab